-92-
6.6 Monitor1 (RWwn)
・
Monitor2 (RWwn+1)
To demand 32-bit data when 2 stations are occupied, specify the lower 16-bit code No.
Use any of the read instruction codes (0101 to 011C) to read the decimal point position (multiplying factor) of the
status indication.
Setting any code No. that is not given in this section will set the error code (
1 ) to respond code (RWrn+2). At
this time, "0000" is set to RWrn, RWrn+1, RWrn+5 and RWrn+6.
Monitor Code No.
Monitored item
Answer Monitor1 data, Monitor2 data
(RWrn, RWrn+1, RWrn+5 and RWrn+6)
(Driver
Programmable PC or PLC...etc)
1 station
occupied
2 stations
occupied
Data length
Unit
0000h
0000h
0001h
0001h
Current position lower 16bit
16bit
10
STM
[mm] or
10
STM
[inch]
0002h
Current position upper 16bit
16bit
0003h
0003h
Command position lower 16bit
16bit
0004h
Command position upper 16bit
16bit
0005h
0005h
Command remaining distance lower 16bit
16bit
0006h
Command remaining distance upper 16bit
16bit
0007h
0007h
0008h
0008h
Point table No.
16bit
[No.]
0009h
000Ah
000Ah
Feedback pulse value lower 16bit
16bit
[pulse]
000Bh
Feedback pulse value upper 16bit
16bit
[pulse]
000Ch
000Dh
000Eh
000Eh
Droop pulse value lower 16bit
16bit
[pulse]
000Fh
Droop pulse value upper 16bit
16bit
[pulse]
0010h
0010h
0011h
0011h
Regenerative load factor
16bit
[%]
0012h
0012h
Effective load factor
16bit
[%]
0013h
0013h
Peak load factor
16bit
[%]
0014h
Instantaneously occurring torque
16bit
[%]
0015h
0015h
ABS counter
16bit
[rev]
0016h
0016h
Motor speed lower 16bit
16bit
0.1[rev/min]
0017h
Motor speed upper 16bit
16bit
0.1[rev/min]
0018h
0018h
Bus voltage
16bit
[V]
0019h
0019h
ABS position lower 16bit
16bit
[pulse]
001Ah
ABS position middle 16bit
16bit
[pulse]
001Bh
001Bh
ABS position upper 16bit
16bit
[pulse]
001Ch
001Ch
Within one-revolution position lower 16bit
16bit
[pulse]
001Dh
Within one-revolution position upper 16bit
16bit
[pulse]
Refer to "LECSC Operation Manua (Simplified Edition)", Section 6.6.1 for the timing chart of monitor.