-58-
5.7.7 Single-Step Feed
In Test mode a single step within point table can be executed.
①
From the “Test” menu select “Single-step Feed”which opens a window for “Single-step feed”. (When using this
function, external input signal operation will be disabled. If controlling using a PLC or other upper level device,
ensure the power is turned off and then on before operation.)
②
Select point table number.
③
Press “Start”.
The actuator will set the position at which the power was turned on as the home position (0), and move towards the
defined point table position.
* Check parameters PA06/PA07 parameters (electronic gear duty) if an unexpected move was observed.
Note
* Home position return cannot be performed in test mode.
In Test mode the default position of the actuator is set as the home position when the power was turned on.It is
therefore possible to drive the actuator past the stroke ends. Please pay particular attention to the position of the
actuator on power up.