Air Dryer
2. Transportation and installation
2.2 Installation
2 - 5
IDF100F~150F-W
This equipment and facility water piping should be easy to disassemble so that the water-cooled
condenser can be cleaned.
2.2.5 Draining piping
- The drain tube is equipped with a polyurethane tube of outside diameter 10mm. Release the draining end
of the tube to atmosphere to let condensate flow into a water outlet.
- Condensate will be drained regularly using compressed air pressure. Fix the draining end of the tube
firmly to prevent it from vibrating during draining.
- Ensure the drain tube does not rise up.
- Do not bend or crush the drain tube. When installing the product, take care not to place the product on the
drain tube.
Warning
- When draining, follow the user’s own procedure to keep operators safe. (E.g. Wear
protective goggles, apron and gloves to prevent contact with the drained condensate.)
-
When oils can enter the drained condensate, waste water treatment is necessary.
Follow the bylaws or rules of the local municipality.
Union
Union
Stop valve (water drainage)
Stop valve (water drainage)
Y-shaped strainer (accessory)
Stop valve
Bypass valve
Facility water outlet
Facility water inlet
Equipment for the facility water