IDX-OM-M051
Air Dryer
2. Transportation and installation
2.4 Reinstallation of the product
2 - 10
IDF100F~150F-W
Removal of pneumatic piping
Clean off any sealant debris after the piping is removed. If any sealant debris gets into the product during
reinstallation, it may lead to cooling failure or other product failures.
[How to release the compressed air]
1.
The bypass valve needs to be opened only if compressed air is necessary while the product is removed.
2.
Close the compressed air inlet valve and outlet valves.
3.
Check the ball valve of the auto drain is open.
4.
Press and hold the flush button at the top of the auto drain to release the internal air pressure from
the product. For details, refer to maintenance of the auto drain in Chapter 4 “4.2 Parts requiring
regular maintenance”.
Removal of facility water piping
Drain the facility water in accordance with [2.3.1 Drainage of the facility water circuit] and remove the piping.
Warning
- Only people who have sufficient knowledge and experience are allowed to perform piping work.
- Before removing piping, be sure to shut off the air supply and the product.
- Do not remove piping with any air pressure remaining internally.
Warning
- Only people who have sufficient knowledge and experience are allowed to perform piping work.
- Before removing piping, be sure to shut off the power supply of the facility, which supplies the
facility water, and this equipment.
- Do not remove piping with any air pressure remaining internally.
Flush button
Heavy-duty auto drain