IDX-OM-M051
Air Dryer
2. Transportation and installation
2.2 Installation
2 - 4
IDF100F~150F-W
2.2.3 Pneumatic piping
- Piping to the compressed air inlet and outlet should be connected with a union type of fitting so that it can
be removed.
- When a pneumatic fitting is connected with the body of the product, hold the pneumatic piping at the body
with a pipe wrench and tighten.
- Do not apply the weight of pipes and excessive force during piping to the product.
- Be careful not to transmit vibration resulting from the compressor.
- When the compressed air inlet temperature exceeds 60
o
C, install an aftercooler behind the air
compressor or decrease the temperature of the area where the air compressor is installed to keep it 60
o
C
or less.
- To prevent foreign matter such as dust from getting in the supply air to the product, flush the piping before
connecting. Dust or oil in the piping can cause cooling failure or other failures of the product. Install a
main line filter to the compressed air source to the product.
- Use a pipe capable of withstanding the specified operating pressure and temperature and connect so
that it will not have leakage.
- Be sure to install a bypass pipe to allow maintenance without stopping the air compressor.
The bypass piping should be prepared by the user.
2.2.4 How to connect the facility water piping
- Piping to the facility water inlet and outlet should be connected with a union type fitting so that it can be
removed.
- When a facility water fitting is connected with the body of the product, hold the facility water piping at the
body with a pipe wrench and tighten.
- Do not apply the weight of pipes and excessive force during piping to the equipment.
Connect the piping so that the inlet temperature of the facility water will be lower than 40
o
C.
- To prevent foreign matter such as dust from getting in the facility water to the equipment, flush the piping
before connecting. Dust or oil in the piping can cause cooling failure or other failures of the equipment.
Connect the attached Y-shaped strainer to the facility water inlet.
- Use a pipe capable of withstanding the specified operating pressure and temperature and connect so
that it will not have leakage.
- Install a water drainage (with a stop valve) for maintenance.
Compressed air inlet (IN)
Compressed air outlet (OUT)
Valve at outlet
Valve at inlet
Union or flange
Union or flange
Bypass valve