1. Name and Function of Parts
1.2 Options of product
1 - 2
IDF100F~150F-W
1.2 Options of product
1.2.1 Anti-corrosive treated copper tube (option C)
This is the option providing a special epoxy paint on the surface of the copper tube to prevent corrosion.
The special epoxy paint is applied to the surface of the copper tube except for the part coated with the
thermal insulator.
If the coating on the surface of the copper tube is damaged when the panel is removed for maintenance,
the anti-corrosion treatment will lose its effect.
Pay attention not to damage the coating.
1.2.2 Medium pressure type (option K)
This is the option that extends the maximum operating pressure to 1.6MPa.
The internal piping material of the product is changed from nylon to metal.
1.2.3 Metal name plate (option P)
This is the option that changes the label identifying the model and specifications of the product to a
metal plate.
1.2.4 Ground fault circuit interrupter (option R)
This is the option providing a built-in ground fault circuit interrupter. Should the product have over
current or ground fault, the power supply will be cut off.
Breaker capacity: 20A
Sensitivity of leak current: 30mA
1.2.5 Timer type solenoid valve with auto drain (option V)
This is the option that controls the solenoid valve for draining with a timer.
It comes with solenoid valve protective strainer and ball valve.
The default setting of the timer is 1.5 seconds for ON and 0.5 minute for OFF.
Do not change the setting of the timer.
If it is changed, there can be water leakage from the secondary side of the product.
1.2.6 Facility water piping direction
The piping direction of the facility water can be specified.
The surface with the switch with lamp is viewed as the front.
Front
Symbol: 4:
Right side
Symbol: 5:
Left side