IDX-OM-M051
Air Dryer
3.Start and stop
3.7 Signal output
3 - 4
IDF100F~150F-W
3.7 Signal output
- The operation signal and error signal are output with dry contact.
Signal output
1. START signal
- At start: Closed
- At stop: Open
(Including FAULT error): Open
2. FAULT signal
- Protective equipment in operation: Closed
- Protective equipment not in operation: Open
∗
If the product is stopped by the overload relay built into the compressor, the FAULT signal will not be
output.
- Contact capacity
Resistance load 2A, Inductive load 80VA, Lamp load 100W
Minimum load: DC5V, 2mA