HRX-MM-L012
Chapter 6 Documents
HRGC Series
6.1 Specifications List
6-1
Chapter 6 Documents
6.1 Specifications List
Table 6-1 Specifications list
Item
HRGC001-
∗
HRGC002-
∗
HRGC005-
∗
Rated ambient temp.
32
°
C (5 to 40
°
C)
Inst
allation
Oper
ating
environment
Humidity range
30 to 70%RH (No condensation)
Fluid used
Fresh water
Rated capacity of tank
10L
20L
Supply voltage
1-phase AC200 to 230v (50/60Hz)
Recommended earth
leakage breaker capacity,
15A 30A
Sensitivity current
30mA
Input
Start/stop command
signal
Remote operation starts upon Contact closed, and stops at contact opened
Cooling water
(only for HR
GC
∗∗∗−
W
∗
)
Cooling water temp.
range
Cooling water pressure
range
Cooling water flow rate
range
Cooling water inlet/ outlet
t pressure differential
5
~
32degC
0.3~0.5MPa
10/12 L/min (50/60Hz)
0.26/0.18MPa (50/60Hz)
5
~
32degC
0.3~0.5MPa
27/28 L/min (50/60Hz)
0.25/0.20Mpa (50/60Hz)
Rated temp. / accuracy of
circulating fluid
20±1.0°C or 0.5°C (Temp. range of circulating fluid: 5 to 35
°
degC)
Rated cooling capacity
0.9/1.1kW(50/60 Hz) 1.9/2.3 kW(50/60 Hz)
4.5/4.8kW (50/60 Hz)
Pumping capacity
10/10 L/min (at 0.13/0.18 MPa)
23/28 L/min(at 0.20/0.24 MPa)
Op. signal
Relay contact ( AC250V of contact capacity, 1A, resistance load. Contact closes during
operation, and contact opens during stop and during power-off.)
Output
Output
signal Emergency stop
signal
Relay contact (AC250V of contact capacity, 1A, resistance load. Contact closes while alarm light
remains OFF and during power-off, and contact opens while alarm light remains ON.)
fault error
(stop function)
System stop function for pump overload (Pump thermal relay)
System stop function for compressor overload (compressor thermal relay)
System stop function for low level in tank (level switch)
System stop function for refrigerant high pressure (level switch)
System stop function for fed water high temp. (set temp. of the controller)
Others
System stop function for fan motor high temp(thermostat with build in fan motor)
System stop function for high temp water in tank(temp. fuse
:
option)
System stop function for water leakage(water leak sensor
:
option)
Protective function
(for equipme
nt)
Alarm
(no stop function)
No stop function for abnormal fed water temp. (set temp. of the controller by user)
External panel
SGCC(Munsell 10Y8/0.5 Urban white)
Control panel
SGCC(DIC183blue)
Base Stainless
steel
Connecting direction
(
Recirculating fluid
)
Stainless steel(tank, connection inlet and outlet,
hose fitting etc), Bronze(manifold
)
,
PVC(Internal refrigerant piping hose),
PPE(pump casing, impeller),
Copper brazing (Heat exchanger)
Stainless steel (tank, pump impeller,
connection inlet and outlet , hose fitting etc)
Bronze(manifold pump casing, etc),
PVC(Internal refrigerant piping hose),
Copper brazing (Heat exchanger)
Wetted part
(
Cooling water
)
Stainless steel (connection inlet and outlet etc, hose fitting), PVC(internal pumping piping hose),
brass(water pressure regulating valve), Cu brazing (Heat exchanger)
Internal refrigerant piping
Copper, Brass, aluminum, Copper brazing, Stainless steel
Material
Operatingre frigerant
R407C (HFC)
Y-shaped strainer1pcs
(HRGC00
※
-W)
Eye bolt M12x4pcs, Y-shaped strainer1pcs(HRGC00
※
-W)
Accessory
(Power supply, signal cable and connected terminal etc wish the business mind by the
customer.)
Weight 75kg
110kg
Содержание HRGC001-A Series
Страница 6: ...HRX MM L012 Contents HRGC Series Contents 4 ...
Страница 15: ...HRX MM L012 Chapter 1 Safety Instructions HRGC Series 1 7 Material Safety Data Sheet MSDS 1 9 ...
Страница 16: ......
Страница 28: ...HRX MM L012 Chapter 3 Error Display and Remedy 3 4 Other Errors HRGC Series 3 8 ...
Страница 74: ...HRX MM L012 Chapter 4 Service Procedure 4 3 Replacement procedure HRGC Series 4 46 ...
Страница 92: ...HRX MM L012 Chapter 5 Service Parts List 5 3 Illustration of service parts HRGC Series 5 18 ...