HRX-MM-L012
Chapter 4 Service Procedure
4.3 Replacement procedure
HRGC Series
4-44
<HRGC005-
∗
5>
Table 4-23 Part number of service parts (3-way proportional valve assembly)
Part number
HRG-S0200
Removal
1.
Open the locking wire saddle and remove the connector [EV1] (option).
2.
Loosen the hose bands (3pcs) and disconnect the hoses.
3.
Remove the 3-way proportional valve assembly. (Fixing screw x 6)
z
When the piping is disconnected or connected, it is turned using a spanner/wrench.
When turning piping, be careful not to twist the wires of the temperature sensor and
3-way proportional valve assembly, as they can break.
z
The product must not be operated until the piping sealant is completely dry.
Otherwise, it can cause fluid leakage.
z
Check the hose is not twisted after connecting.
Fig. 4-22 Removal of 3-way proportional valve assembly
Front side
2.
Hose band
Front side
1.
Connector [EV1] (option)
3-way proportional
valve assembly
Locking wire saddle
3.
Fixing
screw