HRX-MM-L012
Chapter 4 Service Procedure
4.3 Replacement procedure
HRGC Series
4-10
4.3.2
Replacement of pump
<HRGC001-
∗
, HRGC002-
∗
>
Table 4-6 Part number of service parts (pump)
Part number
HRG-S0171
Removal
1.
Open the locking wire saddles (3pcs) and disconnect wires.
2.
Remove the connector [JP] of the pump.
3.
Remove the ground wire. (Screw x 1)
4.
Place the drain pan below the hose, loosen the hose band A to remove the hose A, and
drain water from the pump.
5.
Loosen the hose bands (2pcs) and disconnect the hoses.
6.
Remove the pump. (Nut x 4) Remove the ground wire. (Screw x 1)
Fig. 4-3 Removal of pump
1.
Locking wire
saddle
Front
side
Front side
2.
Connector [JP]
3.
Ground wire
6.
Nut x 4
Pump
4.
Hose band B
Hose B
Hose A
5.
Hose band A