HMC6 Power Management Controller User Manual
Page 77 of 87
No.
Item
Range
Default
Description
10
Reactive Power Control
Voltage
Control
Gain
(0-500) %
20
The internal analog voltage is adjusted to
control the generator voltage after parallel
connection.
Stability
(0-2000) %
20
Relay
Control
Response
(0.1-4.00)Hz/s
1.20
The internal relay is adjusted to control the
generator voltage after parallel connection.
Stability
(0.01-1.60)s
0.20
Gain
(0-30000)%
10
Dead Band
(0-10.0)%
1.0
11
Load Parallel Ramp
Minimum
(0-100.0)%
1.0
The active power percentage of the unit
from soft unloaded to the opening.
12
Fixed Active Power%
(0-100.0)%
30.0
The percentage of active power output in
fixed power mode.
13
Fixed Reactive Power Mode (0-1)
0
0: Power Percentage; 1: Power Factor
14
Fixed Reactive%
(0-100.0)%
8.0
The percentage of reactive power output in
fixed power mode.
15
SG-DG Grid Connection
Time
(0-999.9)s
60.0
The maximum grid connection time of SG
and DG.
16
Fixed Min. On-load%
(0-100.0)%
0.0
When the controller works in both SG mode
and fixed power mode, if the total load is
lower than the active power of fixed output
of SG, the maximum percentage value of
DG, and the remaining power is carried by
SG.
If this value is 0, when the total power is
lower than the fixed active power output of
SG, DG does not start with load.
17
Fixed Max. On-load%
(0-100.0)%
100.0
When the controller works in both SG mode
and fixed power mode, if the total load is
greater than the fixed active power
percentage of SG and DG, DG will be
loaded to the fixed active power
percentage, the remaining power will be
loaded by SG as much as possible and the
maximum load will be the setting value. If
the total load is even greater, it will be
balanced by SG and DG.
18
Max. Load% of SG
Receiving
(0-100.0)%
100.0
When the controller works in both SG mode
and load-receiving mode, if SG on-load
mode is effective, the load must be lower
than receiving rated power percentage( the
setting value) before SG is closing.
19
DG Stop% When SG
(0-100.0)%
50.0
When the controller works in both SG mode