HMC6 Power Management Controller User Manual
Page 48 of 87
No.
Items
Parameter Range
Default
Description
Set
1: Enable
43
Set value
(80-100)%
96
44
Delay
(0.1-100.0)s
5.0
45
Alarm Type (0-5)
1:Warn
46
Under
Frequency 2
Set
Action
(0-1)
0: Disable
1: Enable
1:Enable
47
Set value
(80-100)%
93
48
Delay
(0.1-100.0)s
10.0
49
Alarm Type (0-5)
2:Trip
50
Under
Frequency 3
Set
Action
(0-1)
0: Disable
1: Enable
0:Disable
51
Set value
(80-100)%
92
52
Delay
(0.1-100.0)s
8.0
53
Alarm Type (0-5)
2:Trip
54
ROCOF Set
Action
(0-1)
0: Disable
1: Enable
0:Disable
55
Set value
(0-1.00)Hz/s
0.20
When the controller detects that the
busbar ROCOF has exceeded the set
value, it will initiate an alarm signal and
the alarm information will be displayed
on LCD.
56
Delay
(0-20.0)s
0.1
57
Alarm Type (0-5)
1:Warn
58
VECTOR SHIFT
Action
(0-1)
0: Disable
1: Enable
0:Disable
59
Set value
(0-20.0)°
6.0
When the controller detects that the
busbar VECTOR SHIFT has exceeded
the set value, it will initiate a alarm
signal and the alarm information will be
displayed on LCD.
60
Delay
(0-20.0)s
0.1
61
Alarm Type (0-5)
1:Warn