HMC6 Power Management Controller User Manual
Page 64 of 87
No.
Name
Description
Auto
Mode
Semi-auto
Mode
Manual
Mode
started when the input is active.
31.
Remote Mode
Input
The signal output when the controller is in remote
mode. The engine is remote control status when the
input is active.
●
●
Х
32.
Opened Input
Open breaker feedback input signal; Fail to Open
alarm will be initiated if the controller cannot detect
the signal after the input is active.
●
●
Х
33.
External Adjust
Simulate adjust voltage/frequency input is active
only when the input port is active.
Х
●
Х
34.
Start Inhibit
Semi-start and auto start are inhibited.
●
●
Х
35.
Short Circuit
External over current short circuit input trip.
●
●
Х
36.
Override
Genset is inhibit to trip or shutdown except for over
frequency and over current.
●
●
Х
37.
Shutdown
Trip and stop immediately.
●
●
Х
38.
1
st
Priority
Configure the priority of controller as the highest
level.
●
●
●
39.
2nd Start Input
If it failed to start, this input is active and will issues
start signal again.
●
●
●
40.
System Manual
Mode Input
When input is active, all gensets on the busbar
become manual mode.
●
●
●
41.
System
Semi-auto Mode
When input is active, all gensets on the busbar
become semi-auto mode.
●
●
●
42.
System Auto
Mode Input
When input is active, all gensets on the busbar
becomes auto mode.
●
●
●
43.
System Light
Load Active
When input is active, all gensets on the busbar are
light load.
●
●
Х
44.
System Safety
Mode Input
When input is active, all gensets on the busbar
become safe mode.
●
●
Х
45.
Semi-mode/Auto
Transfer Input
When input is active, auto mode is active;
When input is inactive, semi-auto mode is active.
●
●
●
46.
Prohibit Genset
On-load Input
●
●
Х
47.
Non-auto Mode
HC Allowed
When input is active, in manual mode/semi-auto
mode, if genset capacity meets heavy consumer
request power, it will also output heavy consumer
response, heavy consumer allowed signal.
●
●
●
48.
Limit Network
Connected No.
When input is active, limit genset network
connected number based on configuration (max.
network connected number);
●
●
Х
49.
Engine Running
Feedback
●
●
Х