HMC6 Power Management Controller User Manual
Page 65 of 87
No.
Name
Description
Auto
Mode
Semi-auto
Mode
Manual
Mode
50.
Shore Power
Supply Input
This input is active when shore power supplies.
●
●
●
51.
Disconnector
Open Input
When input port is active, divide a phase of busbar
based on current busbar genset configuration; only
the unit scheduled on this busbar is active.
●
●
Х
52.
Capacity
Insufficient
Reduce Load
Input
When heavy load is requesting, if all normal gensets
are online and still cannot meet requested power; if
this input is active, it will make NEL trip.
●
●
●
53.
Abnormal Trip of
Main Switch
When the input port is active, the controller tripping
alarms.
●
●
●
54.
Numbers of
Running Units
Reserved
When the input port is active, the units with load
running in the network >= numbers of running units
reserved.
●
●
●
55.
Forced Manual
Mode
●
●
●
56.
No Power Loss
of the Ship
No power loss of the ship when the input port is
active.
●
●
Х
57.
Forced Auto
Mode
●
●
Х
58
Reserved
Reserved
59
SG Enabled
If module is not set as SG mode, the controller will
work in SG mode when input port is effective.
●
●
Х
60
SG/DG
Switching
When input port is effective, DG starts on-load,
otherwise, SG starts on-load.
●
●
Х
61
SG Solenoid
Valve Closing
Feedback
When the controller works in SG mode and input
port is effective, SG is allowed to start. Otherwise,
SG is not allowed to start.
●
●
Х
62
Drop Power
Input
When input port is effective, the controller will limit
the max. output power of the genset according to
the set drop value.
●
●
Х
63
SG On-load Input
When input port is active, SG starts on-load and
selects load distribution according to load mode.
●
●
Х
64
DG On-load Input
When input port is active, DG starts on-load and
selects load distribution according to load mode.
●
●
Х
65
DG Inactive Input
When input port is active, all DG are disconnected
and the load is transferred to the other power
supply units.
●
●
Х
66
Busbar Outage
Closing Input
When input port is active, DG controller detects that
the busbar is outage then allows DG switch to
close.
●
●
Х