HMC6 Power Management Controller User Manual
Page 58 of 87
11.6
MODULE SETTING
Table 24– Module Parameter Settings
No.
Items
Parameter Range
Default
Description
Module
1.
Power On Mode
(0-2)
0
0: Semi Auto Mode; 1: Auto Mode;
2: Manual Mode.
2.
Module Address
(1-254)
1
Controller’s address during remote sensing.
3.
Language
(0-2)
0
0: Simplified Chinese 1: English 2: Other.
4.
Password
(0-65535)
00318
For entering advanced parameters setting.
5.
Start Mode
(0-2)
0
0: Linear start; 1: Cycle start; 2: Duty Time
Start
6.
Power Supply Rated
Voltage
(10.0-50.0)V
24.0
To offer standards for detecting of power’s
over/under voltage.
7.
Power Supply Over
Voltage Warn
(50-200)%
130
To offer standards for detecting of
percentage of power’s over voltage.
8.
Power Supply Under
Voltage Warn
(1-100)%
80
To offer standards for detecting of
percentage of power’s under voltage.
9.
Extension Module
DIN16-1 Enabled
(0-1)
0: Disable
1: Enable
0: Disable
Connect with extension module DIN16-1
when input ports of HMC6 are not enough; If
still not enough, the external DIN16-2 is
extended.
10.
Alarm Delay
(0.1~999.9)s
5.0
11.
Extension Module
DIN16-2 Enabled
(0-1)
0: Disable
1: Enable
0: Disable
12.
Alarm Delay
(0.1~999.9)s
5.0
13.
Extension Module
DOUT16-1Enabled
(0-1)
0: Disable
1: Enable
0: Disable
Connect with extension module DOUT16-1
when input ports of HMC6 are not enough; If
still not enough, the external DOUT16-2 is
extended.
14.
Alarm Delay
(0.1~999.9)s
5.0
15.
Extension Module
DOUT16-2Enabled
(0-1)
0: Disable
1: Enable
0: Disable
16.
Alarm Delay
(0.1~999.9)s
5.0
17.
LED Display
Extension Module 1
Enabled
(0-1)
0: Disable
1: Enable
0: Disable
2 Connect with extension module LA16-1
when LED lamps of HMC6 are not enough; If
still not enough, the external LA16-2 is
extended.
18.
Alarm Delay
(0.1~999.9)s
5.0
19.
LED Display
Extension Module 2
Enabled
(0-1)
0: Disable
1: Enable
0: Disable
20.
Alarm Delay
(0.1~999.9)s
5.0
21.
GOV Transducer
Transducer
0
One of GOV analog voltage regulating output