HMC6 Power Management Controller User Manual
Page 55 of 87
No.
Items
Parameter Range
Default
Description
24.
Set Value
(50-300)%
150
25.
Delay
(0.1-999.9)s
10.0
26.
Alarm Type
(0-5)
2:Trip
27.
Overload 1
Protection
Action
(0-1)
0: Disable
1: Enable
1:Enable
28.
Set Value
(80-200)%
120
29.
Delay
(0.1-999.9)s
10.0
30.
Alarm Type
(0-5)
1:Warn
31.
Overload 2
Protection
Action
(0-1)
0: Disable
1: Enable
1:Enable
32.
Set Value
(80-200)%
130
33.
Delay
(0.1-999.9)s
5.0
34.
Alarm Type
(0-5)
2:Trip
35.
Reverse
Power 1
Protection
Action
(0-1)
0: Disable
1: Enable
1:Enable
36.
Set Value
(0-200)%
8
37.
Delay
(0.1-999.9)s
5.0
38.
Alarm Type
(0-5)
1: Warn
39.
Reverse
Power 2
Protection
Action
(0-1)
0: Disable
1: Enable
1:Enable
40.
Set Value
(0-200)%
15
41.
Delay
(0.1-999.9)s
2.0
42.
Alarm Type
(0-5)
2:Trip
43.
Unbalanced
Current Set
Action
(0-1)
0: Disable
1: Enable
1:Enable
44.
Set Value
(0-200)%
20
45.
Delay
(0.1-999.9)s
5.0
46.
Alarm Type
(0-5)
2:Trip
47.
Loss of
Field Set
Action
(0-1)
0: Disable
1: Enable
1:Enable
48.
Set Value
(0-200)%
20
49.
Delay
(0.1-999.9)s
10.0
50.
Alarm Type
(0-5)
1:Warn
51.
NEL 1 Trip
Action
(0-1)
0: Disable
1: Enable
1:Enable
External NEL 1 trip is active when the
active power of any busbar genset has
exceeded the set value.