HMC6 Power Management Controller User Manual
Page 26 of 87
No.
Types
Description
Alarm Type
2
Under Volt
When controller detects the power supply voltage has
fallen below than the set value, it will initiate a warning
alarm.
Warn
Always active
3
Input Port 1~9
When digital input port action selects “Alarm”,
controller sends corresponding alarm signal when the
alarm is active.
Configurable alarm types
It is active in set interval.
4
MSC Too Few
Sets
When the controller detects fewer modules on the MSC
link than the minimum number configured in the unit, it
will initiate a warning alarm. There are 2 possible
reasons: a) Communication line between the
controllers
disconnects,
which
interrupts
communication.
b) Other parallel gen-sets controllers have not been
powered on.
Warn
Always active
5
DIN1 Com Fail
When
the
controller
detects
DIN1
module
communication failure, it will initiate a warning alarm.
Warn
When DIN1 is enabled.
6
DIN2 Com Fail
When
the
controller
detects
DIN2
module
communication failure, it will initiate a warning alarm.
Warn
When DIN2 is enabled
7
DOUT1
Com
Fail
When the controller detects DOUT1 module
communication failure, it will initiate a warning alarm.
Warn
When DOUT1 is enabled
8
DOUT2
Com
Fail
When the controller detects DOUT2 module
communication failure, it will initiate a warning alarm.
Warn
When DOUT2 is enabled
9
LED1 Com Fail
When
the
controller
detects
LED1
module
communication failure, it will initiate a warning alarm.
Warn
When LA1 is enabled
10
LED2 Com Fail
When
the
controller
detects
LED2
module
communication failure, it will initiate a warning alarm.
Warn
When LA2 is enabled
11
HMP300 Com
Fail
When the controller detects HMP300 module
communication failure, it will initiate a warning alarm.
Warn
When HMP300 is enabled