HMC6 Power Management Controller User Manual
Page 50 of 87
No.
Items
Parameter Range
Default
Description
12
Operate Stop Delay
(0-3600)s
1
Stop delay caused by human triggered
(e.g. manual transfer priority, high
consumer request and etc.)
13
Cooling Delay
(0-3600)s
0
High speed cooling time before stop
output.
14
HC Stable Delay
(0-1000)s
5
After busbar retardant power meet with
high consumer request, high consumer
ACK output after this delay.
15
HC ACK Delay
(0-1000)s
5
After busbar retardant power meet with
high consumer request, high consumer
ACK output after “HC Stable Delay”.
11.3
GENERATOR SETTING
Table 21 – Generator Parameter Settings
No.
Items
Parameter Range
Default
Description
Generator
1
AC System
(0-3)
0: 3P4W
0: 3 phase, 4 wire (3P4W);
1: 3 phase, 3 wire (3P3W);
2: 2 phase, 3 wire (2P3W);
3: 1 phase, 2 wire (1P2W).
2
Rated Voltage
(30-30000)V
230
To offer standards for detecting of
generator’s over/under voltage. (It is
primary voltage when using voltage
transformer; it is line voltage when AC
system is 3P3W while it is phase
voltage when using other AC system).
3
Loading Voltage
(0-200)%
95
Setting value is percentage of
generator rated voltage. Detect when
controller prepare loading. When
generator voltage under load voltage,
won’t enter into normally running.
4
Crank Success Volt
(0-200)%
30
To offer standards for detecting crank
disconnect voltage is satisfied or not.
5
Rated Frequency
(10.0-75.0)Hz
50.0
To offer standards for detecting of
over/under/load frequency.
6
Loading Frequency
(0-200)%
85
Setting value is percentage of
generator rated frequency. Detect
when controller prepare loading. When
generator frequency under load
frequency, it won’t enter into normal
running.
7
Crank Success Frequency (0-200)%
65
To offer standards for detecting crank