HGM9120 Genset Controller
HGM9120 Genset Controller Version: 1.0 2014-04-14 Page 51 of 58
9 SENSORS SETTING
1. When reselect sensors, the sensor curve will be transferred into the standard value. For
example, if temperature sensor is SGX (120°C resistor type), its sensor curve is SGX
(120°C resistor type); if select the SGD (120°C resistor type), the temperature sensor
curve is SGD curve.
2. When there is difference between standard sensor curves and using sensor, user can
a
djust it in “curve type”.
3. When input the sensor curve, X value (resistor) must be input from small to large,
otherwise, mistake occurs.
4. If select sensor type as
“None”, sensor curve is not working.
5. If corresponding sensor has alarm switch only, user must
set this sensor as “None”,
otherwise, maybe there is shutdown or warning.
6. The headmost or backmost values in the vertical coordinates can be set as same as
below,
Normal Pressure Unit Conversion Form
pa
kgf/cm
2
bar
psi
1Pa
1
1.02x10
-
5
1x10
-
5
1.45x10
-
4
1kgf/cm
2
9.8x10
4
1
0.98
14.2
1bar
1x10
5
1.02
1
14.5
1psi
6.89x10
3
7.03x10
-
2
6.89x10
-
2
1