HGM9120 Genset Controller
HGM9120 Genset Controller Version: 1.0 2014-04-14 Page 23 of 58
No.
Type
Description
20
High Temp. Warn
When controller detects the temperature is higher than the
set value, it will send warn signal.
21
Low Temp. Warn
When controller detects the temperature is lower than the set
value, it will send warn signal.
22
Pressure
Sensor
Open
When controller detects the sensor is open circuit, and the
action select
“warn”, it will send warn signal.
23
Low OP Warn
When controller detects the oil pressure is lower than the set
value, it will send warn signal.
24
Level Sensor Open
When controller detects the sensor is open circuit, and the
action se
lect “warn”, it will send warn signal.
25
Low Level Warn
When controller detects the oil lever is lower than the set
value, it will send warn signal.
26
Oil
Temperature
Sensor Open
When controller detects the sensor is open circuit, and the
action select
“warn”, it will send warn signal.
27
High Oil Temp. Warn
When controller detects the temperature is higher than the
set value, it will send warn signal.
28
Low Oil Temp. Warn
When controller detects the temperature is lower than the set
value, it will send warn signal.
29
Canopy Temperature
Sensor Open
When controller detects the sensor is open circuit, and the
action
select “warn”, it will send warn signal.
30
High Canopy Temp.
Warn
When controller detects the temperature is higher than the
set value, it will send warn signal.
31
Low Canopy Temp.
Warn
When controller detects the temperature is lower than the set
value, it will send warn signal.
32
Flexible Sensor 1
Open
When controller detects the sensor is open circuit, and the
action
select “warn”, it will send warn signal.
33
Flexible Sensor 1
High
When controller detects the sensor value is higher than the
max. set value, it will send warn signal.
34
Flexible Sensor 1
Low
When controller detects the sensor value is lower than the
min. set value, it will send warn signal.
35
Flexible Sensor 2
Open
When controller detects the sensor is open circuit, and the
action
select “warn”, it will send warn signal.
36
Flexible Sensor 2
High
When controller detects the sensor value is higher than the
max. set value, it will send warn signal.
37
Flexible Sensor 2
Low
When controller detects the sensor value is lower than the
min. set value, it will send warn signal.
38
Digital Input Warn
When digit input port is set as
“warn” and active, controller
sends corresponding warning signal.
39
GSM Com Fail
When select GSM enable but the controller couldn
‟t detect
GSM model, controller sends corresponding warning signal.
40
Earth Current
When the
“Earth current” detection is enabled, if the
controller detects earth current is greater than the set value,
and the action
select “warn”, it will send warn signal.
41
Fuel Usage
When the
“Fuel usage” detection is enabled, if the controller
detects fuel consumption rate is greater than the set value,
and the action
select “warn”, it will send warn signal.