![Smartgen HGM9120 Скачать руководство пользователя страница 58](http://html1.mh-extra.com/html/smartgen/hgm9120/hgm9120_user-manual_1297531058.webp)
HGM9120 Genset Controller
HGM9120 Genset Controller Version: 1.0 2014-04-14 Page 58 of 58
14 FAULT FINDING
Symptoms
Possible Solutions
Controller no response with
power.
Check starting batteries;
Check controller connection wirings;
Check DC fuse.
Genset shutdown
Check the water/cylinder temperature is too high or not;
Check the genset AC voltage;
Check DC fuse.
Controller emergency stop
Check emergence stop button is correct or not;
Check whether the starting battery positive be
connected with the emergency stop input;
Check whether the circuit is open.
Low oil pressure alarm after
crank disconnect
Check the oil pressure sensor and its connections.
High water temp. alarm after
crank disconnect
Check the temperature sensor and its connections.
Shutdown Alarm in running
Check related switch and its connections according to
the information on LCD;
Check programmable inputs.
Crank not disconnect
Check fuel oil circuit and its connections;
Check starting batteries;
Check speed sensor and its connections;
Refer to engine manual.
Starter no response
Check starter connections;
Check starting batteries.
Genset running while ATS not
transfer
Check ATS;
Check the connections between ATS and controllers.