HGM9120 Genset Controller
HGM9120 Genset Controller Version: 1.0 2014-04-14 Page 44 of 58
239
Reserved
7.2.1 CUSTOM PERIOD OUTPUT
Defined Period output is composed by 2 parts, period output S1 and condition output S2.
While S1 and S2 are
TRUE
synchronously, OUTPUT;
While S1 or S2 is
FALSE
, NOT OUTPUT.
Period output S1, can set generator‟s one or more period output freely, can set the delayed
time and output time after enter into period.
Condition output S2; can set as any conditions in output ports.
NOTE:
when delay time and output time both are 0 in period output S1, it is
TRUE
in this
period.
Example,
Output period: start
Delay output time: 2s
Output time: 3s
Condition output contents: output port 1 is active
Close when condition output active/inactive: close when active (disconnect when inactive);
Output port 1 active, after enter “starts time” and delay 2s, this defined period output is
outputting, after 3s, stop outputting;
Output port 1 inactive, defined output period is not outputting.
7.2.2 CUSTOM COMBINED OUTPUT
Defined combination output is composed by 3 parts, condition output S1 or S2 and condition
output S3.
S1 or S2 is
TRUE
, while S3 is
TRUE
, Defined combination output is outputting;
S1 and S2 are
FALSE
, or S3 is
FALSE
, Defined combination output is not outputting.
NOTE:
S1, S2, S3 can be set as any contents except for “defined combination output” in
the output setting.
NOTE:
3 parts of defined combination output (S1, S2, S3) couldn‟t include or recursively