HGM9120 Genset Controller
HGM9120 Genset Controller Version: 1.0 2014-04-14 Page 32 of 58
No.
Items
Parameters
Defaults
Description
6
Safety
On
Delay
(0~3600)s
10
Alarms for low oil pressure, high
temperature, under speed, under
frequency/voltage, charge fail are
inactive.
7
Start
Idle
Time
(0~3600)s
0
Idle running time of genset when
starting.
8
Warming Up
Time
(0~3600)s
10
Warming time between genset switch
on and high speed running.
9
Cooling Time
(0~3600)s
10
Radiating time before genset stop,
after it unloads.
10
Stop
Idle
Time
(0~3600)s
0
Idle running time when genset stop.
11
ETS Solenoid
Hold
(0~3600)s
20
Stop electromagn
et‟s power on time
when genset is stopping.
12
Fail to Stop
Delay
(0~3600)s
0
Time between over of genset idle delay
and stopped when “ETS time” is set as
0;
Time between over of ETS hold delay
and stopped when “ETS Hold output
time” is not 0.
13
After
Stop
Time
(0~3600)s
0
Time between genset stopped and
standby
Engine Setting
1
Engine Type Conventional genset (not J1939)
2
Flywheel
Teeth
(10~300)
118
Tooth number of the engine, for judging
of starter separation conditions and
inspecting of engine speed.
See the
Installation Instructions.
3
Rated Speed
(0~6000)RPM 1500
Offer
standard
to
judge
over/under/loading speed.
4
Speed
on
Load
(0~100)%
90
Setting value is percentage of rated
speed. Controller detects when it is
ready to load. It won‟t switch on when
speed is under loading speed.
5
Loss of Speed
Signal
(0~3600)s
5
Time from detecting speed is 0 to
confirm the action.
6
Loss of Speed
Action
(0~1)
0
0:Warn; 1:Shutdown
7
Over
Speed
Shutdown
(0~200)%
114
Setting value is percentage of rated
speed and delay value can be set.
8
Under Speed
Shutdown
(0~200)%
80
9
Over
Speed
Warn
(0~200)%
110
Setting value is percentage of rated
speed; delay value and return value