HGM9120 Genset Controller
HGM9120 Genset Controller Version: 1.0 2014-04-14 Page 47 of 58
mode;
all
the
keys
except
are inactive, and
will show in the first line of LCD display.
18
Auto Mode Invalid
When input is active, controller won
‟t work under
Auto mode.
key and simulate auto key
input does not work.
19
Reserved
20
Reserved
21
Inhibit Alarm Stop
All shutdown alarms are prohibited except
emergence stop.(Means battle mode or override
mode)
22
Aux Instrument Mode
All outputs are prohibited in this mode.
23
Reserved
24
Reset Maintenance
Controller will set maintenance time and date as
default when input is active.
25
Reserved
26
Aux. High Temp
Connected sensor digital input.
27
Aux. Low OP
Connected sensor digital input.
28
Reserved
29
Remote Start
(Off Load)
In
Auto
mode, when input is active, genset can be
started automatically and NOT take load after
genset normal running; when input is inactive,
genset will stop automatically.
Note: Dedicated remote start input port is fitted (If
active, it is remote start on-load input port).
30
Aux. Manual Start
In
Manual
mode, when input active, genset will
start automatically; when input inactive, genset
will stop automatically
31
Reserved
32
Reserved
33
Simulate Stop key
An external button can be connected and pressed
as simulate panel.
34
Simulate Manual key
35
Reserved
36
Simulate Auto key
An external button can be connected and pressed
as simulate panel.
37
Simulate Start key
38
Simulate G-Load key
This is simulate generator close/open key.
39
Simulate M-Load key
This is simulate mains close/open key.
40
Reserved
41
Reserved
42
Reserved