HGM9120 Genset Controller
HGM9120 Genset Controller Version: 1.0 2014-04-14 Page 37 of 58
No.
Items
Parameters
Defaults
Description
1
Curve Types
(0~15)
7
SGX. See form 4
2
Open Circuit
Action
(0~2)
0
0: Warn; 1: Shutdown; 2: No action
3
High
Temp.
Shutdown
(0~300)ºC
98
Shutdown when sensor temperature
higher than this value. Detecting only
after safety delay is over. The delay
value can be set.
4
High
Temp.
Warn
(0~300)ºC
95
Warn when sensor temperature higher
than this value. Detecting only after
safety delay is over. The delay value
and return value can be set.
5
Low
Temp.
Warn
(0~1)
0
0: Disable; 1: Enable
Canopy Temperature
1
Curve Types
(0~15)
7
SGX. See form 4
2
Open Circuit
Action
(0~2)
0
0: Warn; 1: Shutdown; 2: No action
3
High
Temp.
Shutdown
(0~300)ºC
98
Shutdown when sensor temperature
higher than this value. Detecting only
after safety delay is over. The delay
value can be set.
4
High
Temp.
Warn
(0~300)ºC
95
Warn when sensor temperature higher
than this value. Detecting only after
safety delay is over. The delay value
and return value can be set.
5
Low
Temp.
Warn
(0~1)
0
0: Disable; 1: Enable
Flexible Sensor 1
1
Flexible
Sensor
1
Setting
(0~1)
0
0: Disable 1: Enable; (can be set as
temperature/pressure/liquid
lever
sensor).
Flexible Sensor 2
1
Flexible
Sensor
2
Setting
(0~1)
0
0: Disable; 1: Enable; (can be set as
temperature/pressure/liquid
lever
sensor).
Flexible Input Ports
High Temperature Input
1
Active Type
(0~1)
0
0: Closed to active 1: Open to active
2
Arming
(0~3)
0
0: From safety on 1: From starting
2: Always 3:Never
3
Active Actions (0~4)
0
0: Warn; 1: Shutdown; 2:Trip and stop
3:Trip 4: Indication
4
Active Delay (0~20.0)s
2.0
Time from detecting active to confirm