HGM6100U Series Automatic Control Module
HGM6100U Automatic Genset Controller ISSUE 2014-10-28 Version 1.2 Page 15 of 39
5.2 SHUTDOWN ALARMS
When controller detects shutdown alarm, it will send signal to open switch and stop
genset. The alarms are displayed in LCD.
Shutdown alarms as following,
No.
Items
Description
1
Emergency Stop
When controller detects emergency stop signal, it will send
a stop alarm signal and it will be displayed in LCD.
2
High
Temp.
Shutdown
When the temperature of water/cylinder is higher than set
threshold, controller will send a stop alarm signal and it will
be displayed in LCD.
3
Low Oil Pressure
Shutdown
When oil pressure is lower than threshold, controller will
send a stop alarm signal and it will be displayed in LCD.
4
Over
Speed
Shutdown
When genset speed is higher than set threshold, controller
will send a stop alarm signal and it will be displayed in LCD.
5
Under
Speed
Shutdown
When genset speed is lower than set threshold, controller
will send a stop alarm signal and it will be displayed in LCD.
6
Loss Of Speed
Signal Shutdown
When rotate speed is 0 and delay is not 0, controller will
send a stop alarm signal and it will be displayed in LCD.
7
Genset
Over
Voltage
Shutdown
When genset voltage is higher than threshold, controller will
send a stop alarm signal and it will be displayed in LCD.
8
Genset
Under
Voltage
Shutdown
When genset voltage is under set threshold, controller will
send a stop alarm signal and it will be displayed in LCD.
9
Genset
Over
Current
Shutdown
When genset current is higher than set threshold and delay
is not 0, it will send a stop alarm signal and it will be
displayed in LCD.
10 Fail To Start
Within set start times, if failed to start, controller will send a
stop alarm signal and it will be displayed in LCD.
11
Over Frequency
Shutdown
When genset frequency is higher than set threshold,
controller will send a stop alarm signal and it will be
displayed in LCD.
12
Under Frequency
Shutdown
When genset frequency is lower than set threshold,
controller will send a stop alarm signal and it will be
displayed in LCD.
13 Genset Failed
When genset frequency is 0, controller will send a stop
alarm signal and it will be displayed in LCD.
14 Low Fuel Level
When fuel level low input is active, controller will send a
stop alarm signal and it will be displayed in LCD.
15 Low Water Level
When genset water level low input is active, controller will
send a stop alarm signal and it will be displayed in LCD.