9 SENSOR SETTING
1) When choosing sensor, standard of sensor curve will be needed. If temperature
sensor is set as SGH (120ºC resistor type), sensor curve should be SGH (120
o
C
resistor type); If it is set as SGD (120ºC resistor type), sensor curve should be
SGD curve.
2) If there is difference between standard sensor curve and chosen sensor curve,
select "defined sensor", and then input defined sensor curve.
3) When sensor curve is inputted, X value (resistance) must be in accordance with
the order of higher to lower, otherwise errors will occur.
4) When sensor is selected as "Not used", temperature, pressure and fuel level will
be display as" - - -" in LCD.
5) If there is no pressure sensor, but only has low pressure alarm switch, then you
must set pressure sensor as "Not used", otherwise oil pressure low alarm
shutdown may appear.
6) Can set several points of forehand or backmost as the same ordinate, as the
following picture:
Conventional pressure unit conversion table
1N/m
2
(pa)
1kgf/cm
2
1bar
(1b/in
2
) psi
1Pa
1
1.02x10
-
5
1x10
-
5
1.45x10
-
4
1kgf/cm
2
9.8x10
4
1
0.98
14.2
1bar
1x10
5
1.02
1
14.5
1psi
6.89x10
3
7.03x10
-
2
6.89x10
-
2
1