ALC404 LIGHTING TOWER CONTROLLER USER MANUAL
ALC404 Lighting Tower Controller 2018-11-06 Version 1.1 Page 44 of 83
Category
Parameters
Range
Default
Description
Gen. Under
Frequency Warning
Enable
(0~1)
1
0 Disabled 1 Enabled
Set Value
(0~200)%
84
The setting limit is
percentage of generator
rated frequency.
Return
(0~200)%
86
The setting limit is
percentage of generator
rated frequency.
Delay
(0~3600)s
5
Gen Over
Frequency Warning
Enable
(0~1)
1
0 Disabled 1 Enabled
Set Value
(0~200)%
110
The setting limit is
percentage of generator
rated frequency.
Return
(0~200)%
108
The setting limit is
percentage of generator
rated frequency.
Delay
(0~3600)s
3
Mains
Mains Supply Type
(0~4)
0
0 3Phase 4Wire(3P4W)
1 3Phase 3Wire (3P3W)
2 1Phase 2Wire (1P2W)
3 2Phase 3Wire (2P3W)
4 DC Power
Mains Rated Voltage
(10~1000)V
230
Provide standard for
judging mains over/under
voltage. If voltage
transformer is used, it is PT
primary voltage.If AC
system set as 3P3W, it is
line voltage; and if other AC
system is selected, it is
phase voltage.
Mains Rated Frequency
(10.0~600.0)Hz 50.0
Provide standard for
judging mains over/under
frequency.
Mains Normal Delay
(0~3600)s
10
It is delay time to confirm
mains normal.
Mains Abnormal Delay
(0~3600)s
5
It is delay time to confirm
mains abnormal.
Voltage
Transformer (PT)
Enable
(0~1)
0
0 Disabled 1 Enabled
PT Primary
(10~1000)V
110
PT
Secondary
(10~1000)V
110
Mains Under Voltage
Warning
Enable
(0~1)
1
0 Disabled 1 Enabled
Set Value
(0~200)%
80
The setting limit is