ALC404 LIGHTING TOWER CONTROLLER USER MANUAL
ALC404 Lighting Tower Controller 2018-11-06 Version 1.1 Page 59 of 83
No.
Type
Description
Shutdown
immediate shutdown and controller initiate shutdown alarms.
27 Low Fuel Level Shutdown
If the signal is active after safety on delay expired, genset will
immediate shutdown and controller initiate shutdown alarms.
28
Low Coolant Level
Shutdown
If the signal is active after safety on delay expired, genset will
immediate shutdown and controller initiate shutdown alarms.
29
Oil Pressure Open Circuit
Shutdown
If the signal is active after safety on delay expired, genset will
immediate shutdown and controller initiate shutdown alarms.
30
Temp. Open Circuit
Shutdown
If the signal is active after safety on delay expired, genset will
immediate shutdown and controller initiate shutdown alarms.
31 Reserved
32 Reserved
33 Reserved
34 Reserved
35 Reserved
36 Reserved
37 Reserved
38 Reserved
39 High Temp. Warning Input
It is connect with digital input port of sensor, when the input is active,
controller will initiate warning alarms.
40 Low Oil Pressure Warning
It is connect with digital input port of sensor, when the input is active,
controller will initiate warning alarms.
41 Low Fuel Level Warning
It is connect with digital input port of sensor, when the input is active,
controller will initiate warning alarms.
42
Low Coolant Level
Warning
It is connect with digital input port of sensor, when the input is active,
controller will initiate warning alarms.
43
High Canopy Temp.
Warning
It is connect with digital input port of sensor, when the input is active,
controller will initiate warning alarms.
44 Reserved
45 Reserved
46 Reserved
47 Reserved
48 Reserved
49 External Charge Fail
It is connect with charge fail alarm output port of external charger,
when the input is active, controller will initiate warning alarms.
50 Idle Speed Active
When the input is active, idle speed control starts output. Meanwhile,
generator under voltage/under frequency/ under speed it not
protected.
51 Rise Speed Pulse(ECU)
It is used for EFI engine with CANBUS.
52 Drop Speed Pulse(ECU)
It is used for EFI engine with CANBUS.
53 Idle Pulse input(ECU)
It is used for EFI engine with CANBUS.
54 60Hz Active(ECU)
It is used for EFI engine with CANBUS. When it is active, frequency
is 60Hz.
55 Reserved