ALC404 LIGHTING TOWER CONTROLLER USER MANUAL
ALC404 Lighting Tower Controller 2018-11-06 Version 1.1 Page 56 of 83
7.7
SENSOR SETTING
When reselect sensors, the sensor curve will be transferred into the standard value. For example, if
factory default set as temperature sensor is SGX (120°C resistor type), its sensor curve is SGX (120°C
resistor type); if select the SGD (120°C resistor type), the temperature sensor curve is SGD curve.
When there is difference between standard sensor curves and using sensor, user can a
djust it in ―curve
type‖.
When user defined the sensor curve, X value (resistor) must be input from small to large, otherwise,
mistake occurs.
If select sensor type or sensor curve select
as ―Not Used‖, sensor curve is not working.
The headmost or backmost values in the vertical coordinates can be set as same as below,
Fig. 3
– User Defined Sensor Curve Diagram
Table 24 - Normal Pressure Unit Conversion Form
Item
N/m
2
/ pa
kgf/cm
2
bar
1b/in
2
.psi
1Pa
1
1.02x10
-
5
1x10
-
5
1.45x10
-
4
1kgf/cm
2
9.8x10
4
1
0.98
14.2
1bar
1x10
5
1.02
1
14.5
1psi
6.89x10
3
7.03x10
-
2
6.89x10
-
2
1