ALC404 LIGHTING TOWER CONTROLLER USER MANUAL
ALC404 Lighting Tower Controller 2018-11-06 Version 1.1 Page 46 of 83
Category
Parameters
Range
Default
Description
load.
Light Amount Config.
(1~4)
4
Number of lights that the
system can control
effectively.
Single Light Rated Current
(0.01~99.99)A
4.00
Rated current consumption
for each light, which is used
to provide standard for
judging light fault.
Over Current
Protection
Configure
Enable
(0~1)
1
0 Disabled 1 Enabled
Set Value
(0~200)%
120
The setting value is the
percentage of rated full-load
current.
Action
(1~3)
3
1 Warning
2 Shutdown
3 Trip and Stop
Time
Multiplier
(1~36)
36
The calculate formula of
over current delay can
reference to 7.12
OVER
CURRENT ACTION
Light Fault Check
Configure
Enable
(0~1)
0
0 Disabled 1 Enabled
Single Light
Fault
(0~200)%
75
It is the percentage of rated
current for each light.
Delay
(0~3600)s
5
It is delay time used to
confirm light fault.
Light Fault
Action
(0~3)
1
0 No Action
1 Warning
2 Shutdown
3 Smart Action
Note: Smart action means
controller will prior ensure
lights of tower works
normal, if all lights are fault,
controller will shutdown the
unit, otherwise, controller
only alarms.
Low Fuel Level
Reduce Light
Amount
Enable
(0~1)
0
0 Disabled 1 Enabled
Reduce
Light-on
Amount
Level
(0~1000)%
20
While genset is normal
running, when fuel level
bellows the setting limit,
controller will send fuel level
drop turn off the light
warning signal. Then
controller auto adjust the