ALC404 LIGHTING TOWER CONTROLLER USER MANUAL
ALC404 Lighting Tower Controller 2018-11-06 Version 1.1 Page 16 of 83
No.
Operation Process
Panel Display
3
If engine speed, generator voltage and frequency has
reached on-load requirements (speed
≥ on-load speed,
voltage
≥ on-load voltage and frequency ≥ on-load
frequency), all the lights will illuminate in proper order and the
illumination interval delay is 2s (can be set as 1s ~300s).
4
W
hen ―stop delay‖ time is 00:00:00 manually select 02
Mode Close in Auto Timer Mode screen (01 Mode Start
must be reselect if another time scheduled start is needed)
,
and then press
to confirm the act.
then 1#
~
#4 lights
will off in proper order and the extinguishing interval delay can
be set as 1s
~
300s. The light tower set begin stopping when
all the lights off.
Remark:
The auto timer mode will be canceled automatically when select other auto start mode! if select Auto Timer
Mode(Daily), lighting tower set will be auto started everyday at the pre-set time.
4.5
SUNRISE/SUNSET START OPERATION
4.5.1 SUNRISE/SUNSET START MODE SETTINGS
Table 8
– Sunrise/Sunset Start Operation
No.
Process
Description
Panel Display
1
Download city
info via PC
software
Users should connect PC and ALC400
controller using USB communication line and test
ALC404 software, procedures are as follows:
Open
test
software
—edit
config.
—set
sunrise/sunset
—select
city/user-defined
city
information (longitude, latitude and time zone)
—
download PC software information to the
controller. After download finished, choose any
/
Auto Timer Mode (Daily)
Start Time 18:30:00
Current Time 06:30:39
Cooling Delay 29s
1
2
3
4
Time Left
00:00:00
Start Time 18:30:00
Current Time 06:30:00
4# Light Off 2s
1
2
3
4
Time Left
11:58:48
Start Time 18:30:00
Current Time 18:31:11
Gens Normal Running
1
2
3
4
Time Left
11:58:57
Start Time 18:30:00
Current Time 18:31:02
3# Light On 2s
1
2
3