Configuration
3.31
Figure 3.33 – Transducer Block – Backup/Restore
Transducer Display – Configuration
NOTE
The Transducer Display Configuration screen of the Profibus View is similar to Simatic PDM
screen.
Using the Profibus View or Simatic PDM is possible to configure the Display Transducer block. As
the name described it is a transducer due the interfacing of its block with the LCD hardware.
The Transducer Display is treated as a normal block by any configuration tool. It means, this block
has some parameters and those ones can be configured according to customer's needs.
The customer can choose up to six parameters to be shown at LCD display they can be parameters
just for monitoring purpose or for acting locally in the field devices by using a magnetic tool. The
seventh parameter is used to access the physical device address. The user can change this
address according to his application. To access and configure the Display Block, please, go to the
main menu select "Device OnLine Configuration - Display Block":
Figure 3.34 – Display Block
Display Transducer Block
The local adjustment is completely configured by Profibus View or Simatic PDM. It means, the user
can select the best options to fit his application. From factory, it is configured with the options to set
the Upper and Lower trim, for monitoring the input transducer output and check the Tag. Normally,
the transmitter is much better configured by Profibus View or Simatic PDM, but the local functionality
of the LCD permits an easy and fast action on certain parameters, since it does not rely on
communication and network wiring connections. Among the possibilities by Local Adjustment, the
following options can be emphasized: Mode block, Outputs monitoring, Tag visualization and Tuning
Parameters setting.
The interface between the user is described very detailed on the "General Installation, Operation
and Maintenance Procedures Manual". Please take a detailed look at this manual in the chapter
related to "Programming Using Local Adjustment". It is significantly the resources on this transducer
display, also all the Series 303 field devices from SMAR has the same methodology to handle with
it. So, since the user has learned once, he is capable to handle all kind of field devices from SMAR.
This parameter is used
to save or restore the
default, factory or user
configuration stored at
the sensor module.
By selecting
the options
contained in
the list box,
operations of
backup and
restore data in
the sensor
module can
be selected.
Содержание LD303
Страница 1: ...Profibus PA Pressure Transmitter L D 3 0 3 M E...
Страница 8: ...LD303 Operation and Maintenance Instruction Manual VIII...
Страница 15: ...Installation 1 7 Figure 1 1 f Dimensional Drawing and Mounting Position Sanitary Transmitter with Extension...
Страница 22: ...LD303 Operation and Maintenance Instruction Manual 1 14...
Страница 26: ...LD303 Operation and Maintenance Instruction Manual 2 4...
Страница 49: ...Configuration 3 23 Figure 3 24 Block Mode for Totalizer Block Figure 3 25 Set Reset for Totalizer Block...
Страница 74: ...LD303 Operation and Maintenance Instruction Manual 4 6 Figure 4 4 Exploded View...
Страница 83: ...Maintenance Procedures 4 15 Figure 4 8 TPE Software Screen...
Страница 102: ...LD303 Certifications Information A 4 CSA NEMKO and EXAM CEPEL NEPSI...
Страница 104: ...LD303 Certifications Information A 6 CEPEL...
Страница 105: ...Appendix A A 7 Control Drawing Factory Mutual FM...
Страница 106: ...LD303 Certifications Information A 8...
Страница 108: ...LD303 Operation and Maintenance Instruction Manual B 2...