No.
Name
Description
Value
Explanation
Default
Value
232.08
GdVldTm
Minimum observation
time for line voltage
and frequency in the
permissible range for
connection in s (expert
mode, protected by
SMA Grid Guard)
5 s to 900 s
VDE-AR-N 4105
AS4777
✓
✓ 60 s
220 V / 60 Hz
300 s
232.09
GdMod
Type of reverse feeding
into the utility grid (ex-
pert mode, protected
by SMA Grid Guard)
GridFeed
Charge and feed-
back on utility grid
If
ApplSel
was set to
OnGrid
in the QCG,
the value
GridFeed
is fixed.
If
ApplSel
was set to
OffGrid
in the QCG,
GridFeed
and
GridCharge
can be
selected.
✓
✓
–
GridCharge
Charge on utility grid
232.10
GdRvPwr
Maximum grid reverse
power in W (expert
mode)
0 W to 5000 W
One Sunny Island or
single-cluster system
✖
✓ 100 W
0 W to 20000 W Multicluster system
100 W
232.11
GdRvTm
Permissible time for
maximum grid reverse
power in s (expert
mode)
0 s to 60 s
–
✖
✓ 5 s
232.12
GdVtgMinDel Lower voltage differ-
ence for valid grid con-
nection in V (expert
mode, protected by
SMA Grid Guard)
0.0 V to 20.0 V
VDE_AR_4105
✓
✓ 11.5 V
AS4777
2.0 V
Off-grid
2.0 V
Other
2.0 V
220 V / 60 Hz
2.0 V
232.13
GdVt-
gMaxDel
Upper voltage differ-
ence for valid grid con-
nection in V (expert
mode, protected by
SMA Grid Guard)
0.0 V to 12.0 V
VDE_AR_4105
✓
✓ 11.5 V
AS4777
2.0 V
Off-grid
2.0 V
Other
2.0 V
220 V / 60 Hz
2.0 V
13 Parameters in Sunny Remote Control
SMA Solar Technology AG
Operating Manual
131
SI30M-44M-60H-80H-BE-en-33