No.
Name
Description
Value
Explanation
Default
Value
233.06
GdTm1Str
Start of standard addi-
tional time period for grid
request in hh:mm:ss (ex-
pert mode)
00:00:00 to
23:59:59
‒
✖
✓
‒
233.07
GdTm2Str
Start of additional time pe-
riod for grid request in h-
h:mm:ss (expert mode)
00:00:00 to
23:59:59
–
✖
✓
–
233.08
GdPwrEna
Grid request based on
power (expert mode)
Disable
Disable
✖
✓ Disable
Enable
Enable
233.09
GdPwrStr
Grid request for connec-
tion power limit in kW (ex-
pert mode)
233.10 GdPwrStp
to
300 kW
‒
✖
✓ 4.0 kW
233.10
GdPwrStp
Grid request for discon-
nection power limit in kW
(expert mode)
0 kW to
233.09 GdPwrStr
–
✖
✓ 2.0 kW
233.11
GdStrChrgMo
d
Grid request based on
charge mode (expert
mode)
Off
Off
✖
✓ Equal
Full
Full charge
Equal
Equalization
charge
Both
Full and
equalization
charge
234# Gen Control
No.
Name
Description
Value
Explanation
Default
Value
234.01
GnVtgMin
Lower minimum threshold
of PV array voltage for
voltage monitoring in V
(expert mode)
172.5 V to
210.01 InvVtgNom
–
✖
✓ 172.50 V
234.02
GnVtgMax
Upper maximum thresh-
old of PV array voltage
for voltage monitoring
in V (expert mode, pro-
tected by
SMA Grid Guard)
210.01 InvVt-
gNom to 264.5 V
‒
✖
✓ 250.0 V
13 Parameters in Sunny Remote Control
SMA Solar Technology AG
Operating Manual
SI30M-44M-60H-80H-BE-en-33
136