132# Grid State
No.
Name
Description
Value
(Plain text
no.)
Explanation
132.01
GdStt
Utility grid status (expert mode) Off (1)
Off; Grid operation is dis-
abled.
✓
✓
Init (2)
Initialization; Utility grid has
been detected.
Detect (3)
Grid monitoring started.
Wait (4)
Waiting until the stand-alone
grid is synchronized with the
utility grid.
RunVExt (5)
Grid operation without feed-
back; The stand-alone grid is
synchronized with and con-
nected to the utility grid.
Feed (6)
Grid operation with feed-back;
Grid feed-in into the utility grid
is possible.
Silent (7)
Energy-saving in the utility grid;
the Sunny Island is in energy-
saving mode.
SiStr (8)
The Sunny Island is switching
to energy-saving mode.
SiStp (9)
The Sunny Island is leaving en-
ergy-saving mode.
Error (10)
An error occurred when con-
necting.
Reinit (11)
Initialization; Utility grid has
been detected again.
132.02
GdRmgTm
Standby time to feed-in in hh:m-
m:ss
This is the remaining time of
grid monitoring in hh:mm:ss
–
–
✓
✓