– Set the thresholds for voltage and frequency of the generator voltage (see the Sunny Island inverter
installation manual).
If the symbol is displayed permanently, the Sunny Island is in the warm-up period or is blocked for connection.
Useful hint: Tip: Check whether the Sunny Remote Control displays the "
!
" warning symbol in standard mode.
Why does the Sunny Island connect to the generator for only a short time?
The generator may be overloaded.
• Select the parameter
234.03 GnCurNom
and set it to 75% of the rated current of the generator.
• If possible, reduce the power of the loads.
The maximum permissible generator voltage may be set too low.
• Select the parameter
234.02 GnVtgMax
and set to the maximum generator voltage.
The minimum frequency for the generator voltage may be set too high.
• Select the parameter
234.05 GnFrqMin
and set to the minimum frequency of the generator voltage.
The permitted time
234.14 GnRvTm
for reverse power might have been exceeded.
• Check whether warning
W401
is registered in the menu
420# Error history
.
Useful hint: Tip: If a warning was registered, the warning symbol "
!
" is shown in the standard mode of the
Sunny Remote Control.
• Select the
540.02 GnAck
parameter and set to
Ackn
. This acknowledges the generator error.
The Sunny Island does not reconnect to the generator after disconnection from the generator due
to non-compliance with the thresholds for voltage and frequency – why?
The Sunny Island is switched with a hysteresis, i.e., the thresholds for connection do not correspond to the thresholds
for disconnection.
• To unload the generator, disconnect unnecessary loads.
• Wait until the voltage and frequency have reached the nominal values.
10.6.5 Questions Regarding Multicluster Systems
Extension clusters remain in standby mode even though the main cluster is in inverter mode?
The data cable between the masters of the individual clusters might not be connected. The master of the main cluster
cannot forward the "Start" command to the masters of the extension clusters.
Why is the multicluster system not supplying full power?
An extension cluster or individual Sunny Island inverters of an extension cluster might have failed.
Why are high levels of energy being transferred between the clusters in the multicluster system?
The state of charge of the batteries might differ temporarily. The off-grid system equalizes different states of charge
automatically.
The nominal frequencies and nominal voltages may be defined differently.
• Set the frequencies and voltages in the
210# Inverter Settings
menu to the same values for all masters.
The battery capacities might differ significantly.
• Distribute the battery capacities to the clusters as evenly as possible.
10 Troubleshooting
SMA Solar Technology AG
Operating Manual
SI30M-44M-60H-80H-BE-en-33