13.2.2.3 External/Backup (230#)
231# General
No.
Name
Description
Value
Explanation
Default
Value
231.01
PvFeedTmStr
Start time for PV grid feed-
in in hh:mm:ss (expert
mode)
00:00:00 to
23:59:59
–
✖
✓ 04:00:00
231.02
PvFeedTmStp
Stop time for PV grid feed-
in in hh:mm:ss (expert
mode)
00:00:00 to
23:59:59
–
✖
✓ 22:00:00
231.03
ExtLkTm
Lock time until connection
to the external grid after
reverse power or relay
protection in minutes (ex-
pert mode)
0 min to
60 min
–
✖
✓ 20 min
231.06
ExtSrc
External energy sources in
Off-Grid mode
PvOnly
Only AC sources in
the stand-alone grid,
no generator in the off-
grid system
✖
✓
–
Gen
Generator
Grid
Utility grid
GenGrid
Electric generator or
utility grid
231.12
ClstPwrNom
Nominal power of the
cluster in kW
–
–
✓
✓
–
232# Grid Control
No.
Name
Description
Value
Explanation
Default
Value
232.01
Country
Set country standard
(protected by
SMA Grid Guard)
Other
Individual setting
✓
✓
–
VDE-AR-4105
Code of Practice
VDE-AR-N 4105
–
AS4777
Standard AS4777
232.02
GdVtgMin
Lower minimum thresh-
old of line voltage for
voltage monitoring in V
(expert mode, pro-
tected by
SMA Grid Guard)
172.50 V to
210.01 InvVt-
gNom
230 V / 50 Hz
✓
✓ 184.00
V
220 V / 60 Hz
194.00
V
13 Parameters in Sunny Remote Control
SMA Solar Technology AG
Operating Manual
129
SI30M-44M-60H-80H-BE-en-33