No.
Name
Level Cause
Corrective measures
W 843 ComBoxWD
1
The SBUKomBox (Meter Box)
watchdog has triggered.
• Contact the Service (see Section 16
W 844 eHZ1ProtFail
1
Unsupported protocol detected
on eHZ 1 (feed-in & purchased
electricity meter)
W 845 eHZ2ProtFail
1
Unsupported protocol detected
on eHZ 2 (PV production meter)
W 846 eHzInFail
1
Reading heads of the eHZ inter-
changed in the input of the
SBUKomBox (Meter Box).
• Swap the optical probe
connections.
W 847 ComHMFaill
1
CAN communication with en-
ergy meter is faulty.
• Ensure that the data cables are
correctly installed.
• Ensure that the parameter
250.06 ComBaud
is set to
115k Bd
.
W 848 PhsMtrComFail
1
Faulty communication between
the Sunny Island and the
SMA Energy Meter: Electric
power per line conductor is not
available.
• Ensure that the data cables are
correctly installed.
• Ensure that the current firmware
version of the SMA Speedwire data
module is installed.
W 851 Sic1BatShort
1
Battery reversely connected
or short circuit on PV charge
controller 1
: Connection of the
battery to the Sunny Island
Charger 1 is reverse-poled or
there is a short circuit.
• Ensure that the battery is correctly
connected to the
DC
connection of
the Sunny Island Charger charge
controller.
• Disconnect the PV array from the
Sunny Island Charger and restart
the system. This will ensure that the
PV array is not short-circuited.
W 852 Sic1BatVtgHi
1
PV charge controller 1 bat-
tery overvoltage
: Battery volt-
age at the Sunny Island Charg-
er 1 is too high.
1. Ensure that the configuration of the
Sunny Island Charger charge
controller with the DIP switches is
correct.
2. Ensure that all DC sources and DC
loads are correctly configured and
connected.
3. Reset the off-grid system. Disconnect
the off-grid system, wait ten minutes
and restart.
10 Troubleshooting
SMA Solar Technology AG
Operating Manual
77
SI30M-44M-60H-80H-BE-en-33