No.
Name
Description
Value
Default
Value
223.07
BatPro3Soc
Battery SOC for protection mode level 3
as % (expert mode)
0% to 70%
✖
✓
10 %
223.08
BatProTmm
Minimum time (in minutes) during which
there is no battery current for switching to
battery protection mode (expert mode)
If the minimum time has elapsed and no
battery current was present, the Sunny Is-
land can switch to battery protection
mode.
1 min to 20 min
✖
✓
5 min
224# BatSilent
No.
Name
Description
Value
Explanation
Default
value
224.01
BatSilentEna
Energy-saving mode
Enable
Enable
✖
✓
Disable
Disable
Disable
224.02
BatSilentTmFlo
Time until switchover to
energy-saving mode (h)
1 h to 48 h
–
✖
✓
3 h
224.03
BatSilentTmMax
Maximum duration of en-
ergy-saving mode (h)
1 h to 168 h
✖
✓
12 h
225# Current Sensor
No.
Name
Description
Value
Explanation
Default
value
225.01
BatCurSnsTyp
Type of battery current
sensor
None
No sensor is
connected.
✓
✓ None
60 mV
60 mV type
50 mV
50 mV type
225.02
BatCurGain60
60 mV type in
A
/
60 mV
0
A
⁄
60 mV
to
1800
A
⁄
60 mV
–
✓
✓ 100
A
⁄
60 mV
225.03
BatCurGain50
50 mV-Typ in
A
⁄
50 mV
0
A
⁄
50 mV
to
1800
A
⁄
50 mV
–
✓
✓ 100
A
⁄
50 mV
225.04
BatCurAutoCal
Automatic calibration of
external battery current
sensor
Start
Start automatic
calibration
✓
✓
–
13 Parameters in Sunny Remote Control
SMA Solar Technology AG
Operating Manual
SI30M-44M-60H-80H-BE-en-33
128