8 Commissioning
SMA Solar Technology AG
Operating manual
SHP-US-20-BE-en-10
44
Parameter name
Value/range
Default value
Voltage monitoring lower
maximum threshold
(Over-
voltage/Slow)
510 V to 720 V
660 V
Voltage monitoring lower
max. threshold trip. time
(Overvoltage/Slow, maximum
time)
100 ms to 60000 ms
1000 ms
Voltage monitoring upper
minimum threshold
(Under-
voltage/Slow)
270 V to 600 V
528 V
Voltage monitoring upper
min. threshold trip. time
(Un-
dervoltage/Slow, maximum
time)
100 ms to 60000 ms
2000 ms
Voltage monitoring of me-
dian minimum threshold
(Un-
dervoltage/Fast)
270 V to 600 V
300 V
Voltage monitoring median
min. threshold trip.time
(Un-
dervoltage/Fast, maximum
time)
100 ms to 60000 ms
160 ms
Voltage monitoring of lower
minimum threshold as RMS
value
270 V to 600 V
300 V
Voltage monitoring of lower
min.threshold as RMS value
for tripping time
100 ms to 60000 ms
160 ms
Frequency monitoring me-
dian maximum threshold
50 Hz to 66 Hz
66 Hz
Frequency monitoring me-
dian maximum threshold,
tripping time
(Overfrequency,
maximum time)
0 ms to 1000000 ms
1000 ms
Frequency monitoring lower
maximum threshold
(Over-
frequency)
50 Hz to 66 Hz
60.5 Hz
Frequency monitoring lower
maximum threshold, trip-
ping time
0 ms to 1000000 ms
160 ms