8 Commissioning
SMA Solar Technology AG
Operating manual
SHP-US-20-BE-en-10
45
Parameter name
Value/range
Default value
Frequency monitoring upper
minimum threshold
(Under-
frequency)
44 Hz to 60 Hz
59.3 Hz
Frq. monitoring upper min.
threshold trip. time
(Underfre-
quency, maximum time)
0 ms to 300000 ms
160 ms
Frequency monitoring me-
dian minimum threshold
44 Hz to 60 Hz
57 Hz
Frequency monitoring me-
dian minimum threshold,
tripping time
0 ms to 300000 ms
160 ms
Voltage increase protection
480 V to 638 V
576 V
Voltage increase protection
tripping time
40 ms to 10000 ms
1000 ms
Min. voltage for reconnec-
tion
270 V to 600 V
530 V
Max. voltage for reconnec-
tion
600 V to 798 V
635 V
Grid nominal voltage
480 V to 690 V
600 V