DOL 434 LPV
Technical Manual
23
Wind direction maximum voltage
Wind speed minimum voltage
Wind speed maximum voltage
Wind speed minimum speed
Wind speed maximum speed
Enter a Minimum value as well as a Maximum value to indicate the
area within which the weather station can measure.
Figure 3: Offset of the location of the house - north being the point of orientation.
4.2.2 Calibration of pressure sensor
Depending on the control type (positive pressure/negative pressure), for which the DOL 18 is to be used, it must
be installed and adjusted in different ways.
When installing the pressure sensor, dip switches must be set up and tubes must be placed. Also see the Cir-
cuit Diagrams and Cable Plans document.
System type
Minimum value (Pa)
Maximum value (Pa)
Negative pressure
0
100
Positive pressure
- 50
50
Bio filter
0
300
Table 3:
Recommended values
Select the menu
Technical | Calibration | Climate | Pressure sensor
Setting the minimum and maximum values must only be done
when setting up the sensor.