DOL 434 LPV
26
Technical Manual
Relay-controlled light
Enter the measured lux value for ON.
Set each calibration point individually.
ON and OFF for relay-controlled light.
Points 1-6 for light dimmer (0-10 V controlled).
Light dimmer
Enter a lux value which corresponds to the measured light level
at the given voltage.
4.4 Calibrating light sensor
When using a DOL 16 light sensor, you can calibrate the sensor against the current light in the livestock house.
Measure the light level (lux meter) in an area inside the live-
stock house where you would like to determine the light level
(not where the sensor is positioned).
Compare the value with the values in the documentation for
DOL 16.
Enter the measured value in the menu
| Technical |
Calibration | Production | Light sensors | Input calibration in-
strument value.