Max. reduction at outside
temperature
Setting the outside temperature where the minimum ventilation is not further
reduced.
Outside temperature
Minimum ventilation
Outside temperature range where the minimum ventilation is reduced
Outside temperature
Minimum ventilation
Figure 17: Reduction of minimum ventilation at low outside temperature
The reduction increases linearly (from 0 % at 5 °C, 20 % at -2.5 °C to 40 % at -10 °C).
At an outside temperature of -2.5 °C, a minimum ventilation of 30 % is thus reduced by 20 %, giving a reduction
of 6 %.
6.5.7 CO2 minimum ventilation
P band
Working range of the sensor.
Integration time
Reaction timer of the sensor.
Longer time: slow reaction.
Shorter time: faster reaction.
6.5.8 NH3 ventilation
P band
Working range of the sensor.
Integration time
Reaction timer of the sensor.
Longer time: slow reaction.
Shorter time: faster reaction.
6.6 Adjustment of pressure
6.6.1 Negative pressure curve
Based on the current ventilation requirement, the controller adjusts pressure by adjusting air inlets and air out-
lets in relation to each other.