DOL 434 LPV
16
Technical Manual
3.7.2.3.1 Setup examples
Number of chim-
neys
Low
High
0 - 28,800 m3/h
low speed.
28,800 m3/h - 62,000 m3/h
high speed.
Fan output is controlled at high speeds by a sig-
nal from a 0-10 volts output.
Stepless
1
7200
15500
MS1
1
7200
15500
MS2
2
14400
31000
Total
4
28800
62000
Table 2:
4 exhaust units with variable DA 600 LPC-13 fans.
The set-up requires this installation.
Stepless unit
Variable ON/OFF
Variable ON/OFF
Flap: stepless
Fan: Stepless
Flap: ON/OFF
Fan: stepless
Flap: ON/OFF
Fan: stepless
Low
High
All flaps are 100% open and the fan
speed is increased stepless on all units
parallel from low to high.
Low
High
Figure 2: Dynamic MultiStep. All fans are variable.
3.7.2.4 Parking of fans
With this function, fans can be taken temporarily out of service. This can, for example, be used in cold periods
where some fans are closed for insulation purposes, or if a fan is defective and awaiting repair.