DOL 434 LPV
Technical Manual
33
5.2.3 Testing management functions
5.2.3.1 Testing of current sensor
This section is only relevant to livestock houses where supply current sensors are installed.
The testing must show that the current sensor is connected to the requested fan.
Select the menu
Technical | Manual/auto.
The current voltage can be seen in the menu
Management | Current sensors
.
Select the individual fans in the menu
Manual/Auto | Climate | Outlet
one by one.
Activate the fan. Check that the current sensor shows power consumption.
Then deactivate the fan. Check that the current sensor does not show power consumption.
5.2.3.2 Testing auxiliary sensor
This section is only relevant to livestock houses where auxiliary sensors are installed.
Check that the current voltage displayed corresponds to what you can measure on the sensor or the connection
terminals with a multimeter.
5.3 Testing Network Connection
If the controller is integrated in a network which can be accessed through the PC management program Far-
mOnline Explorer, the individual controllers must be visible in FarmOnline. Also see FarmOnline Explorer Tech-
nical Manual regarding testing of the network connection.