EA230-K-30 – Functions
Operating Manual
Chain actuator – EA-K-30/xxx-T(-DA)
Chain actuator
– EA230-K-30/xxx(-S)
BA_EA(230)-K-30-XXX_EN_12
www.simon-protec.com
Date: 13.02.2019
Issue: 1.2 / 01.2019
Page 10
5.7 LED displays
The EA230-K-30 has three status LEDs (see Figure 2: “EA230-K-30/xxx(-S) chain actuator” on page 5) with the following
meanings.
Red LED
Number
of
flashes
Type of error
Possible solution
1
Overload cut-off
• Check the drives for correct installation
(mechanical / electrical);
• Is the force of the installed actuators adequate.
2
Communication error (Synchro)
• Perhaps there are actuators connected that do not have a
common RESET.
• Check the red / white connection cable;
• Perform a RESET procedure for the interconnected
actuators.
3
—
—
4
Inconsistent DIP switch settings (Synchro)
• The DIP switch settings of the interconnected actuators do
not match.
• Check and correct the DIP switch settings.
5
Error during the RESET procedure
• Repeat the RESET procedure.
6
Cabling error (Synchro)
• The power input of the the interconnected actuators does
not match.
• Check and correct the connection of the actuators.
7
Addressing error (Synchro)
• The assignment of the internal addresses of interconnected
actuators has failed.
• Perform a RESET procedure.
8
Power supply error
• The supply voltage is not within the permissible range or is
not stable.
• Check the electrical connection;
• Check the supply voltage.
9
Chain alignment error (Synchro)
• The chain position (STROKE) of the interconnected
actuators is not within the permissible range
• Perform a RESET procedure.
10
Memory error (Synchro)
• The storage process in the internal memory was not
successful.
• Repeat the RESET procedure.
11
Connection error
• A RESET procedure is performed at the same time in the
case of several non-synchronous actuators.
• Perform the RESET procedures individually.
Green LED
LED status
Meaning
Continuously
lighting
The voltage supply to the actuator is correct.
The actuator is closed correctly and the storage of the STROKES has been performed successfully.
Flashing
The voltage supply to the actuator is correct.
The set STROKE has been reached. The number of flashes indicates the internal address to which the actuator
has been assigned during the RESET procedure in the case of synchronous actuators.