Mounting — EA-K-30 Electrical connection
Operating Manual
Chain actuator – EA-K-30/xxx-T(-DA)
Chain actuator
– EA230-K-30/xxx(-S)
Page 21
BA_EA(230)-K-30-XXX_EN_12
www.simon-protec.com
Date: 13.02.2019
Issue: 1.2 / 01.2019
6.2.8 DUO operation / parallel connection
A maximum of
2 actuators
can be operated in parallel in
DUO operation
(via a connection cable) with the associated tandem.
A maximum of
4 actuators
can be operated
in parallel
with the associated tandem (e.g. on large wings).
If an actuator stops due to overloading, the actuator connected in parallel is also stopped after a predetermined run-on time (see
Table 1: “Electrical properties” on page 24 and Figure 10: “Configurable ranges” on page 8).
DUO operation:
Connect the cables according to the connection plan.
blue
T
NO1
S
1. actuator (DA)
brown
NO2
O
black
yellow
red
blue
T
NO1
S
2. actuator
brown
NO2
O
red
O
S
T
blue
brown
red
connected
internally
connection cable
black
yellow
black
yellow
24
V
DC
OPE
N
: S = +
O = - CLOSE: pole change
volt-free contact
(max. 28 V / 1.0 A)
tandem-port
(electr. insulate)
EA-K-30/xxx-T
EA-K-30/xxx-T-DA
connect
ion cabl
e
power c
onnectio
n cable
Parallel connection:
Connect the cables according to the connection plan.
24
V
DC
T
NO1
S
OPE
N
: S = +
O = - CLOSE: pole change
1. actuator
NO2
O
volt-free contact
(max. 28 V / 1.0 A)
T
NO1
S
2. actuator
NO2
O
volt-free contact
(max. 28 V / 1.0 A)
blue
brown
black
yellow
red
blue
brown
black
yellow
red
up to
4 actuators
at all
ATTENTION
The actuators run at the same time, the power supply and the cable dimensions must be adapted to the total current of the
system.
ATTENTION
Only connect 2 actuators to each other. Maximum cable length of 10 m between the actuators.
ATTENTION
Only connect 4 actuators in parallel to each other. Maximum cable length of 10 m between two actuators.