G12
Siemens Energy & Automation, Inc. 1000 McKee Street Batavia, Illinois 60510
SFIM-7002A-0901
Section G, September, 2001
E “Standard Trip” Heater Elements for Ambient Temp. Comp. Bimetal Relays
Min
Max
Size 0 & 1
0.67
0.72
E14
1
0.73
0.80
E16
2
0.81
0.85
E17
2
0.86
0.92
E18
2
0.93
0.99
E19
2
1.00
1.08
E23
2
1.09
1.23
E24
3
1.24
1.37
E26
3
1.38
1.54
E27
3
1.55
1.69
E28
3
1.70
1.80
E29
3
1.81
1.94
E31
3
1.95
2.07
E32
3
2.08
2.26
E33
3
2.27
2.54
E34
3
2.55
2.69
E36
5
2.70
2.88
E37
5
2.89
3.14
E38
5
3.15
3.40
E39
5
3.41
3.81
E41
5
3.82
4.26
E42
5
4.27
4.62
E44
7
4.63
5.09
E46
10
5.10
5.61
E47
10
5.62
5.91
E48
10
5.92
6.15
E49
10
6.16
6.70
E50
10
6.71
7.54
E51
10
7.55
8.29
E52
25
8.30
8.99
E53
25
9.00
9.85
E54
25
9.86
10.4
E55
25
10.5
12.0
E56
25
12.1
13.6
E57
25
Size 1 only
D25385-7
Full Load
Motor Amps
Heater
Code
No.
Max. Rat.
of Prot.
Device*
13.7
15.6
E60
30
15.7
17.0
E61
30
17.1
18.4
E62
30
18.5
19.4
E65
30
19.5
21.3
E66
30
21.4
24.4
E67
40
24.5
25.9
E69
40
26.0
26.0
E70
40
Min
Max
Size 1¾
2.27
2.54
E34
3
2.55
2.69
E36
5
2.70
2.88
E37
5
2.89
3.14
E38
5
3.15
3.40
E39
5
3.41
3.81
E41
5
3.82
4.25
E42
5
4.26
4.62
E44
7
4.63
5.09
E46
10
5.10
5.61
E47
10
5.62
5.91
E48
10
5.92
6.15
E49
10
6.16
6.70
E50
10
6.71
7.54
E51
10
7.55
8.29
E52
25
8.30
8.99
E53
25
9.00
9.85
E54
25
9.86
10.4
E55
25
10.5
12.0
E56
25
12.1
13.6
E57
25
13.7
15.6
E60
30
15.7
17.0
E61
30
17.1
19.4
E62
30
19.5
20.9
E65
30
21.0
22.2
E66
40
22.3
25.3
E67
40
25.4
26.9
E69
40
27.0
30.2
E70
40
30.3
33.3
E72
40
D25556-3
Size 2 & 2½
10.5
12.0
E56
50
12.1
13.6
E57
50
13.7
15.6
E60
50
15.7
17.1
E61
50
17.2
19.4
E62
50
19.5
20.9
E65
50
21.0
22.2
E66
50
22.3
25.3
E67
50
25.4
26.9
E69
50
27.0
30.2
E70
50
30.3
33.3
E72
50
33.4
35.3
E73
50
35.4
41.5
E74
50
41.6
45.0
E76
100
Size 2½ only
D26069-5
Full Load
Motor Amps
Heater
Code
No.
Max. Rat.
of Prot.
Device*
Min
Max
Size 3 & 3½
30.0
33.5
E69
100
33.6
36.4
E70
100
36.5
39.6
E71
100
39.7
43.6
E73
100
43.7
46.5
E73A 100
46.6
51.6
E74
100
51.7
54.4
E76
100
54.5
58.0
E77
100
58.1
63.0
E78
100
63.1
67.7
E79
100
67.8
72.4
E80
100
72.5
80.0
E94
100
Size 3½ only
D26801-3
Size 4
56.9
60.9
E89
250
61.0
63.9
E91
250
64.0
67.7
E92
250
67.8
72.4
E93
250
72.5
77.7
E94
250
77.8
85.9
E96
250
86.0
91.9
E97
250
92.0
96.7
E98
250
96.8
105
E99
250
106
115
E103 250
116
130
E104 250
D36024-2
Full Load
Motor Amps
Heater
Code
No.
Max. Rat.
of Prot.
Device*
80.1
88.1
E96
150
88.2
91.5
E97
150
91.6
96.8
E98
150
96.9
99.0
E99
150
99.1
108
E101
150
Min
Max
Size 4½ & 5
88.0
98.0
E27
400
98.1
108
E28
400
109
114
E29
400
115
122
E31
400
123
130
E32
400
131
140
E33
400
141
155
E34
400
156
166
E36
400
167
177
E37
400
178
193
E38
400
Size 5 only
D25651-5
Size 6
166
195
E27
600
196
217
E28
600
218
229
E29
600
230
245
E31
600
246
261
E32
600
262
281
E33
600
282
311
E34
600
312
331
E36
600
332
355
E37
600
356
387
E38
600
388
419
E39
600
420
467
E41
600
468
500
E42
600
D25665-3
Full Load
Motor Amps
Heater
Code
No.
Max. Rat.
of Prot.
Device*
194
209
E39
400
210
233
E41
400
234
248
E42
400
45.1
52.3
E77
100
52.4
55.7
E78
100
Heaters shown in the table provide a maxi-
mum trip rating of 125% of the motor name-
plate amperes, which is suitable for 40°C
motors. For all other motors select heaters
one code number lower than specified in the
table, which give a maximum trip rating of
approximately 115%.
The tripping current of any heater in a 40°C
ambient is 25% greater than the lower value
of motor amperes shown in the table.
Starters do not provide protection from short
circuits. A protective device should be pro-
vided in accordance with the NEC (CEC in
Canada) and not exceed the values shown in
the table.
Note: If the rating specified is not a standard
size for the circuit breaker manufacturer, use
the next largest size.
*
Ratings specified are for instantaneous
trip circuit breakers.
Maximum current rating for thermal-
magnetic circuit breakers is 250% of
maximum heater FLA.
Maximum current rating of fuses is:
a. 150% of maximum heater FLA for
Class R, K, or L (time delay).
b. 250% of maximum heater FLA for
Class K or L (non-time delay).
c. 300% of maximum heater FLA for
Class J (non-time delay).
If the calculated rating is between standard
sizes, the next larger size may be used. Fuse
size may not exceed switch size.
Wye-delta starters:
If the motor nameplate
shows the full load delta line current only,
divide this value by 1.73 or multiply by .58 to
select the proper heater rating.
Hazardous voltage.
Can cause death, serious person-
al injury, or property damage.
Automatic reset will continue to reset on
two-wire control. When not desired, use
three-wire control.
Do not use manual trip button when relay
is set in automatic reset position.
Fire, electric shock, or explosion hazard.
Can cause death, serious injury or
property damage.
To provide continued protection against risk of fire or
electric shock, examine and if damaged replace cur-
rent-carrying parts and other components of combi-
nation controller. Tripping (opening) of branch-circuit-
protective device may be an indication that fault cur-
rent has been interrupted. If overload relay current
elements burn out, replace complete overload relay.
To maintain overcurrent, short circuit and ground
fault protection, follow manufacturer’s instructions
for selecting current elements and setting instanta-
neous trip circuit breaker.
Содержание TIASTAR SFIM-70020
Страница 63: ......
Страница 64: ......
Страница 65: ......
Страница 66: ......
Страница 67: ......
Страница 68: ......
Страница 69: ......
Страница 70: ......
Страница 71: ......
Страница 72: ......
Страница 73: ......
Страница 74: ......
Страница 75: ......
Страница 76: ......
Страница 77: ......
Страница 78: ......
Страница 79: ......
Страница 80: ......
Страница 81: ......
Страница 82: ......
Страница 83: ......
Страница 84: ......
Страница 85: ......
Страница 86: ......
Страница 87: ......
Страница 88: ......
Страница 96: ...4 ...
Страница 100: ...5 Today and tomorrow you ll know you have the very best ...
Страница 115: ...13 Siemens Energy Automation Inc ...
Страница 116: ...14 Siemens Energy Automation Inc ...
Страница 117: ...15 Siemens Energy Automation Inc ...